فحص الدائرة القائمة
تحقّق من دائرة مركّبة: الكابل، والجهاز، والهبوط، وZs.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
جرّب مشروعاً 7
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check the breaker on a 4 mm² circuitWhether a 32 A breaker suits 4 mm² cable, and the largest breaker the cable allows.
- Check an existing three‑phase submainWhether 16 mm² on a 63 A breaker over 80 m passes the cable, drop and Zs checks.
- Check a 20 A breaker on 2.5 mm²Whether a 20 A breaker suits a 2.5 mm² circuit.
- Check a 32 A breaker on 6 mm²Whether a 32 A breaker suits a 6 mm² circuit.
- Check a 16 A breaker on 1.5 mm²Whether a 16 A breaker suits a 1.5 mm² circuit.
- Check a 63 A breaker on 16 mm²Whether a 63 A breaker suits 16 mm² mains.
- Check a 10 A breaker on 1 mm²Whether a 10 A breaker suits a 1 mm² lighting circuit.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- الأطوار
- طور واحد
- الجهد
- 230 V
- تيار التصميم
- 20 A
- معامل القدرة
- 0.9
- المعيار
- NZ · AS/NZS 3008.1.2
- طول المسار
- 30 m
- طريقة التركيب
- داخل حاوية في الهواء
- درجة الحرارة المحيطة
- 30 °C
- الدوائر المجمّعة
- 1
- حجم الكابل المركب
- 2.5 mm²
- المادة
- النحاس
- العزل
- PVC 75 °C
- الأسلاك الداخلية
- متعدد القلوب
- الكابلات المتوازية
- 1
- حد هبوط الجهد
- 5 %
- المعاوقة الخارجية Ze
- 0.35 Ω
- تيار العطل المتوقع
- 0 kA
- منحنى الجهاز
- المنحنى C
- القيمة الاسمية للجهاز
- 20 A
الدائرة على 2.5 mm²
ينجح
- التصنيف المصحح Iz
- 23A
- هبوط الجهد
- 4.25%
- معاوقة حلقة عطل التأريض
- 0.89Ω
- أقصى Zs للجهاز
- 1.53Ω
- أصغر مقاس ينجح
- 2.5mm²
- أكبر جهاز بمنحنى C يسمح به الكابل
- 20A
- معامل التصحيح المجمّع
- ×1.00
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- مقاس الموصل المركّب2.5mm²
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- التقنين الجدولي لـ 2.5 mm²23A
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- معامل تصحيح المحيط×1.00
AS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88
- معامل تصحيح التجميع×1.00
One circuit, no grouping factor
- معامل التصحيح المجمّع×1.00
- التصنيف المصحح Iz23A
AS/NZS 3000:2018 Cl 3.4
- هبوط الجهد9.78V
- نسبة هبوط الجهد4.25%
AS/NZS 3000:2018 Cl 3.6.2
- تصنيف الجهاز In20A
AS/NZS 3000:2018 Cl 2.5.3.1
- حجم موصل الأرضي2.5mm²
AS/NZS 3000:2018 Table 5.1
- معاوقة حلقة عطل التأريض عند 230 V، طور إلى تأريض0.89Ω
AS/NZS 3000:2018 Table 8.1
- أقصى Zs للجهاز1.53Ω
AS/NZS 3000:2018 Table 8.1
- أصغر مقاس يحقق الشرط2.5mm²
AS/NZS 3000:2018 Cl 3.4
حول هذه الحاسبة
How this is calculated
The tool takes a circuit that is already installed and runs the five checks of the cable size calculator at its size. It uses the same code, so the two tools agree on every size.
- Current capacity. It reads the tabulated rating of the installed size for your material, insulation, core count and installation method. It multiplies the rating by the correction factors for the route to get Iz. Iz must be at or above the design current Ib.
- Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set.
- Breaker rating. The breaker rating In must sit between the two: Ib at or below In, and In at or below Iz. The tool gives both margins.
- Loop impedance. It adds the active and earth conductor resistance to the external impedance Ze. The total Zs must stay under the maximum for the breaker curve and rating.
- Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time.
- Result. The circuit passes when every check it runs passes. The tool gives the smallest standard size that passes with the same breaker, and the largest breaker of the same curve that the cable allows.
| Step | Table or clause | What it decides |
|---|---|---|
| Current rating | Table 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single core | The tabulated rating of the installed size |
| Correction factors | Tables 22 to 29 and Table 2 | The factors for the route |
| Voltage drop | Tables 30, 34 and 35, AS/NZS 3000 Cl 3.6.2 | The drop over the run and its limit |
| Breaker rating | AS/NZS 3000 Cl 2.5.3.1 | That In sits between Ib and Iz |
| Earth and Zs | AS/NZS 3000 Table 5.1 and Table 8.1 | The earth conductor size and the maximum loop impedance |
| Fault withstand | Table 52 and Cl 5.3 | The fault current the conductor survives |
Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section.
Common circuits, worked with the tool
Each line states its circuit. Every line uses multicore copper cable with PVC insulation and one circuit on the route, enclosed in air at 30 °C. Every breaker is a C curve and Ze is 0.35 Ω, on the New Zealand tables.
- Socket‑outlets, 2.5 mm² on a 20 A breaker over 30 m. It passes every check. The drop is 4.25 %, close to the 5 % limit.
- The same cable on a 32 A breaker with a 25 A load. It fails the current, drop and breaker checks. 6 mm² is the smallest size that passes.
- 4 mm² on a 32 A breaker over 20 m. It fails the breaker check, because Iz is 29 A. The largest breaker the cable allows is 25 A, and 6 mm² is the smallest size that passes on 32 A.
- Three‑phase submain, 16 mm² on a 63 A breaker over 80 m. It fails on loop impedance: Zs is 0.76 Ω against a maximum of 0.49 Ω. With this breaker, 70 mm² is the smallest size that passes.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The breaker and Zs rules come from AS/NZS 3000, which is the same in both countries.
What the tool does not check
The tool works from the inputs, not from a test. Measure Ze and Zs on site and compare the reading with the maximum it gives. It does not check RCD rules or discrimination between breakers.
To size a new circuit, use the cable size calculator. To read the factors for a route on their own, use the correction factors calculator.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
أي مقاس قاطع يمكن وضعه على كابل 4 mm²؟
يعتمد ذلك على المسار. عند وضعه داخل حاوية في هواء 30 °C بمفرده، يبلغ تصنيف نحاس 4 mm² في نيوزيلندا 29 A، لذلك يكون قاطع 25 A أكبر مقاس قياسي. يخفّضها التجميع أو الحرارة أو العزل. أدخل مسارك لقراءة أكبر قاطع يسمح به الكابل.
ماذا تعني Ib ≤ In ≤ Iz؟
Ib هو تيار التصميم للحمل، وIn القيمة الاسمية للقاطع، وIz القيمة الاسمية للكابل بعد التصحيح. يجب أن يحمل القاطع الحمل، وأن يحمل الكابل القيمة الاسمية للقاطع. يحدد AS/NZS 3000 Clause 2.5.3.1 هذه القاعدة.
لماذا تفشل دائرة طويلة في معاوقة الحلقة؟
للكابل الطويل أو الصغير معاوقة حلقة عطل التأريض عالية. عندئذ يكون تيار العطل منخفضاً جداً بحيث لا يفصل القاطع عند إعداده المغناطيسي في الوقت المناسب. استخدم كابلاً أكبر، أو قيمة اسمية أقل للقاطع، أو منحنى B، أو راجع قواعد RCD الخاصة بالدائرة.
هل تقيس الأداة دائرتي؟
لا. تعمل من مقاس الكابل والمسار والمعاوقة الخارجية Ze التي تدخلها. قِس Ze وZs في الموقع، وقارن القراءة بأقصى Zs الذي تعطيه الأداة.
ما المقاس الذي تقترحه الأداة عندما تفشل الدائرة؟
أصغر مقاس قياسي يكون مطابقاً في كل فحص مع القاطع نفسه والمسار نفسه والحمل نفسه. وهو الجواب الذي تعطيه حاسبة مقاس الكابل للدائرة نفسها.
أمثلة محلولة
- A circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.
- What size breaker for 4 mm² cable4 mm² copper enclosed in air takes a 25 A breaker, and 32 A fails at an Iz of 29 A. Grouping, a hot ceiling, insulation and a long run lower it.
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 Cl 2.5.3.1Protective device coordination
- AS/NZS 3000:2018 Cl 3.4Current-carrying capacity
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
- AS/NZS 3008.1.2:2017 Table 4Current ratings, single‑core cable, two cables per circuit, thermoplastic 75 °C
- AS/NZS 3008.1.2:2017 Table 5Current ratings, single‑core cable, two cables per circuit, cross-linked 90 °C
- AS/NZS 3008.1.2:2017 Table 7Current ratings, single‑core cable, three cables per circuit, thermoplastic 75 °C
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 27 Sept 2026.
أدوات ذات صلة
- حاسبة مقاس الكابلFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة معاوقة حلقة عطل التأريضCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- أداة اختيار الكابل المبسّطةRead the Appendix C device rating and voltage drop tables.AS/NZS 3000
هل كان هذا مفيداً؟
سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.