AS/NZS 3008.1.2:2017
Table 28(1), 28(2)
Rating factors for depth of laying
The cable size and correction factors tools read the factor for how deep the cable is buried. It applies only to buried cables.
Na-verify: binasa laban sa naka-print na standard, mga pahina 89. Na-check noong 24 Sept 2026.
Mga unit: Depth m
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
10 na row
| Depth (m) | Buried direct up to 50 | Buried direct 50 to 300 | Buried direct over 300 | Underground enclosure single core | Underground enclosure multicore | Factor |
|---|---|---|---|---|---|---|
| 0.5 | 1 | 1 | 1 | 1 | 1 | 1 |
| 0.6 | 0.99 | 0.98 | 0.97 | 0.98 | 0.99 | 0.99 |
| 0.8 | 0.97 | 0.96 | 0.94 | 0.95 | 0.97 | 0.97 |
| 1 | 0.95 | 0.94 | 0.92 | 0.93 | 0.96 | 0.95 |
| 1.25 | 0.94 | 0.92 | 0.9 | 0.9 | 0.95 | 0.94 |
| 1.5 | 0.93 | 0.91 | 0.89 | 0.89 | 0.94 | 0.93 |
| 1.75 | 0.92 | 0.89 | 0.87 | 0.88 | 0.94 | 0.92 |
| 2 | 0.91 | 0.88 | 0.86 | 0.87 | 0.93 | 0.91 |
| 2.5 | 0.9 | 0.87 | 0.85 | 0.86 | 0.93 | 0.9 |
| 3 | 0.89 | 0.86 | 0.83 | 0.85 | 0.92 | 0.89 |