AS/NZS 3008.1.2:2017
Table 28(1), 28(2)
Rating factors for depth of laying
The cable size and correction factors tools read the factor for how deep the cable is buried. It applies only to buried cables.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 89. I tirohia 24 Sept 2026.
Ngā unit: Depth m
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
10 rārangi
| Depth (m) | Buried direct up to 50 | Buried direct 50 to 300 | Buried direct over 300 | Underground enclosure single core | Underground enclosure multicore | Factor |
|---|---|---|---|---|---|---|
| 0.5 | 1 | 1 | 1 | 1 | 1 | 1 |
| 0.6 | 0.99 | 0.98 | 0.97 | 0.98 | 0.99 | 0.99 |
| 0.8 | 0.97 | 0.96 | 0.94 | 0.95 | 0.97 | 0.97 |
| 1 | 0.95 | 0.94 | 0.92 | 0.93 | 0.96 | 0.95 |
| 1.25 | 0.94 | 0.92 | 0.9 | 0.9 | 0.95 | 0.94 |
| 1.5 | 0.93 | 0.91 | 0.89 | 0.89 | 0.94 | 0.93 |
| 1.75 | 0.92 | 0.89 | 0.87 | 0.88 | 0.94 | 0.92 |
| 2 | 0.91 | 0.88 | 0.86 | 0.87 | 0.93 | 0.91 |
| 2.5 | 0.9 | 0.87 | 0.85 | 0.86 | 0.93 | 0.9 |
| 3 | 0.89 | 0.86 | 0.83 | 0.85 | 0.92 | 0.89 |