Depth (m)Buried direct up to 50Buried direct 50 to 300Buried direct over 300Underground enclosure single coreUnderground enclosure multicoreFactor
0.5111111
0.60.990.980.970.980.990.99
0.80.970.960.940.950.970.97
10.950.940.920.930.960.95
1.250.940.920.90.90.950.94
1.50.930.910.890.890.940.93
1.750.920.890.870.880.940.92
20.910.880.860.870.930.91
2.50.90.870.850.860.930.9
30.890.860.830.850.920.89