Skip to content
AmpSize

AS/NZS 3008.1.1:2025

Table 3.46, 3.47

Correction factors for depth of laying

The cable size, correction factors and DC cable size tools read the burial depth factor here for a buried route.

Verified: read against the printed standard, pages 85–86. Checked 27 Sept 2026.

Units: Depth m

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.1:2025 page

10 rows

Table 3.46, 3.47, Correction factors for depth of laying
Depth (m)Buried direct up to 50Buried direct 50 to 300Buried direct over 300Underground enclosure single coreUnderground enclosure multicoreFactor
0.5111111
0.60.990.980.970.980.990.99
0.80.970.960.940.950.980.97
10.950.930.920.930.960.95
1.250.940.920.890.910.950.94
1.50.930.90.870.890.940.93
1.750.920.890.860.880.940.92
20.910.880.850.870.930.91
2.50.90.870.840.860.920.9
30.890.850.820.850.910.89

Tools that read it (4)