Skip to content
AmpSize

AS/NZS 3008.1.1:2017

Table 27(1), 27(2)

Rating factors for air and soil ambient temperature

The cable size and correction factors tools read the Australian ambient factor when the Standard is AU and the Edition is 2017. The factors sit on a 40 °C air base, so 40 °C on site applies no reduction.

Verified: read against the printed standard, pages 88. Checked 24 Sept 2026.

Units: Temp °C

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.1:2017 page

41 rows

Table 27(1), 27(2), Rating factors for air and soil ambient temperature
InsulationMediumConductor temp CTemp (°C)Factor
PVCair75151.35
PVCair75201.28
PVCair75251.21
PVCair75301.14
PVCair75351.07
PVCair75401
PVCair75450.91
PVCair75500.82
PVCair75550.72
PVCair75600.6
PVCair75650.49
PVCair75700.37
XLPEair90151.26
XLPEair90201.2
XLPEair90251.15
XLPEair90301.1
XLPEair90351.05
XLPEair90401
XLPEair90450.94
XLPEair90500.88
XLPEair90550.81
XLPEair90600.73
XLPEair90650.65
XLPEair90700.57
XLPEair90750.47
XLPEair90800.34
XLPEair90850.19
PVCsoil75101.14
PVCsoil75151.1
PVCsoil75201.05
PVCsoil75251
PVCsoil75300.95
PVCsoil75350.89
PVCsoil75400.83
XLPEsoil90101.11
XLPEsoil90151.07
XLPEsoil90201.03
XLPEsoil90251
XLPEsoil90300.97
XLPEsoil90350.93
XLPEsoil90400.89