Whakawhiti ki te ihirangi
AmpSize

AS/NZS 3008.1.2:2017

Table 27(1), 27(2)

Rating factors for air and soil ambient temperature

The cable size and correction factors tools read the factor for the air or ground temperature on the route. A hot route lowers the current the cable can carry.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 88. I tirohia 24 Sept 2026.

Ngā unit: Temp °C

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3008.1.2:2017

41 rārangi

Table 27(1), 27(2), Rating factors for air and soil ambient temperature
InsulationMediumConductor temp CTemp (°C)Factor
PVCair75151.18
PVCair75201.12
PVCair75251.06
PVCair75301
PVCair75350.94
PVCair75400.88
PVCair75450.8
PVCair75500.72
PVCair75550.63
PVCair75600.53
PVCair75650.43
PVCair75700.32
XLPEair90151.15
XLPEair90201.09
XLPEair90251.05
XLPEair90301
XLPEair90350.95
XLPEair90400.91
XLPEair90450.85
XLPEair90500.8
XLPEair90550.74
XLPEair90600.66
XLPEair90650.59
XLPEair90700.52
XLPEair90750.43
XLPEair90800.31
XLPEair90850.17
PVCsoil75101.04
PVCsoil75151
PVCsoil75200.95
PVCsoil75250.91
PVCsoil75300.86
PVCsoil75350.81
PVCsoil75400.75
XLPEsoil90101.04
XLPEsoil90151
XLPEsoil90200.96
XLPEsoil90250.93
XLPEsoil90300.91
XLPEsoil90350.87
XLPEsoil90400.83

Ngā taputapu e pānui ana i tērā (3)

Ngā aratohu me ngā whārangi ako e whakahua ana i tēnei (11)