Công cụ tính chiều dài mạch tối đa
Tuyến dài nhất mà sụt áp và mạch vòng sự cố cho phép.
Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 26 Sept 2026.
Thử một công việc 6
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Find the longest run for a lighting circuitThe longest route a 1.5 mm² lighting circuit on a 10 A breaker can take.
- Find the longest socket circuitThe longest run for a 20 A circuit on 2.5 mm².
- Find the longest oven circuitThe longest run for a 32 A circuit on 6 mm², by voltage drop.
- Find the longest motor circuitThe longest three‑phase run on a 16 A D‑curve breaker.
- Find the longest run at 3 %The longest run when the drop limit is 3 %.
- Find the longest heat pump runThe longest run for a 16 A C‑curve circuit on 2.5 mm².
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Dây pha
- 2.5 mm²
- Dây dẫn nối đất
- 2.5 mm²
- Cách điện
- PVC
- Thiết bị bảo vệ
- Máy cắt loại B
- Định mức thiết bị
- 20 A
- Các pha
- Một pha
- Điện áp pha danh định
- 230 V
- Dòng thiết kế
- 20 A
- Hệ số công suất
- 0.9
- Giới hạn sụt áp
- 5 %
Chiều dài tuyến lớn nhất
35.26m
- Chiều dài tuyến vòng lặp sự cố
- 128m
- Chiều dài tuyến sụt áp
- 35.26m
- Kiểm tra bộ điều tốc
- Sụt áp
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Chiều dài tuyến vòng lặp sự cố128m
AS/NZS 3000:2018 Table B1
- Điện trở của dây dẫn đồng ở nhiệt độ vận hành9.01Ω/km
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- Điện kháng0.1Ω/km
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- Sụt áp trên mỗi ampe mét16.31mV/A·m
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- Giới hạn sụt áp được lấy từ điện áp230V
AS/NZS 3000:2018 Cl 3.6.2
- Giới hạn sụt áp11.5V
AS/NZS 3000:2018 Cl 3.6.2
- Chiều dài tuyến sụt áp35.26m
AS/NZS 3000:2018 Cl 3.6.2
- Chiều dài điều tốcKết quả35.26m
AS/NZS 3000:2018 Cl 3.6.2
Giới thiệu công cụ tính này
How this is calculated
The tool finds the longest final subcircuit route that two limits each allow. It reports which limit governs. It reads AS/NZS 3000:2018 and AS/NZS 3008.1.2:2017.
- Fault loop length. The tool reads the route length for your breaker, size and earth size from Table B1.
- Resistance and reactance. It reads these for the active conductor. The tables are Table 30 and Tables 34 and 35, for copper at operating temperature.
- Millivolts per ampere metre. It combines both values with your power factor.
- Voltage drop limit. Cl 3.6.2 sets the limit. You enter it as a percentage of the supply voltage.
- Voltage drop length. It finds the route length at which the drop equals the limit for your design current.
- Governing length. The shorter of the two lengths is the maximum route length.
| Step | Table or clause | What it decides |
|---|---|---|
| Fault loop length | AS/NZS 3000:2018 Table B1 | The longest route for the breaker to trip |
| Cable data | AS/NZS 3008.1.2:2017 Tables 30, 34 and 35 | Resistance and reactance |
| Voltage drop length | AS/NZS 3000:2018 Cl 3.6.2 | The longest route within the drop limit |
Worked example
- 2.5 mm² on a 20 A type B breaker. The earth is 2.5 mm², with PVC insulation, on a single‑phase 230 V supply. The design current is 20 A at a power factor of 0.9. The fault loop route length is 128 m. The voltage drop route length is 35.26 m. The voltage drop governs, so the maximum route length is 35.26 m.
Limits
The tool assumes copper conductors. The reactance is the Table 30 value for a multicore cable. A single‑core run reads a higher reactance for its formation.
The tool does not check the current rating of the cable. It does not add correction factors. Use the cable size calculator for the full check.
See also: Maximum length of a 20 A final subcircuit, The voltage drop limit in Cl 3.6.2 and the voltage drop calculator.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Công cụ Chiều dài mạch tối đa làm gì?
Công cụ báo hai chiều dài. Thứ nhất là chiều dài tuyến mà thiết bị bảo vệ vẫn cắt được kịp thời. Thứ hai là chiều dài mà sụt áp đạt giới hạn của bạn. Chiều dài ngắn hơn trong hai chiều dài quyết định tuyến cáp.
Hai chiều dài lấy từ đâu?
Chiều dài mạch vòng sự cố lấy từ AS/NZS 3000:2018 Table B1 cho thời gian cắt 0.4 s tại 230 V, được quy đổi theo điện áp danh định của bạn. Chiều dài sụt áp dùng điện trở và điện kháng từ AS/NZS 3008.1.2:2017 Tables 30, 34 và 35, đối chiếu với Clause 3.6.2.
Vì sao một tổ hợp không hiển thị chiều dài mạch vòng sự cố?
Table B1 liệt kê cố định các cặp dây dẫn và định mức thiết bị. Cặp không được in trong bảng sẽ không có chiều dài tra cứu, nên công cụ chỉ báo chiều dài sụt áp. Hãy dùng công cụ Tổng trở mạch vòng để kiểm tra tổ hợp đó.
Các điều khoản và bảng mà công cụ này đọc
- B1Maximum route lengths for conductor sizes and protective devices
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 26 Sept 2026.
Công cụ liên quan
- Công cụ tính tiết diện cápFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Công cụ tính sụt ápCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Công cụ tính tổng trở mạch vòng sự cố chạm đấtCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
Thông tin này có hữu ích không?
Có câu hỏi, hoặc giá trị có vẻ sai? Liên hệ chúng tôi.