حاسبة أقصى طول للدائرة
أطول مسار يسمح به هبوط الجهد وحلقة العطل.
Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 26 Sept 2026.
جرّب مشروعاً 6
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Find the longest run for a lighting circuitThe longest route a 1.5 mm² lighting circuit on a 10 A breaker can take.
- Find the longest socket circuitThe longest run for a 20 A circuit on 2.5 mm².
- Find the longest oven circuitThe longest run for a 32 A circuit on 6 mm², by voltage drop.
- Find the longest motor circuitThe longest three‑phase run on a 16 A D‑curve breaker.
- Find the longest run at 3 %The longest run when the drop limit is 3 %.
- Find the longest heat pump runThe longest run for a 16 A C‑curve circuit on 2.5 mm².
المدخلات
مثال محلول بالمدخلات الافتراضية.
- الموصل الحي
- 2.5 mm²
- موصل الأرضي
- 2.5 mm²
- العزل
- PVC
- جهاز الحماية
- قاطع دائرة من النوع B
- القيمة الاسمية للجهاز
- 20 A
- الأطوار
- طور واحد
- جهد الطور الاسمي
- 230 V
- تيار التصميم
- 20 A
- معامل القدرة
- 0.9
- حد هبوط الجهد
- 5 %
أقصى طول للمسار
35.26m
- طول مسار حلقة العطل
- 128m
- طول مسار هبوط الجهد
- 35.26m
- فحص التحكم
- هبوط الجهد
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- طول مسار حلقة العطل128m
AS/NZS 3000:2018 Table B1
- مقاومة الموصل النحاسي عند درجة حرارة التشغيل9.01Ω/km
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- المفاعلة0.1Ω/km
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- هبوط الجهد لكل أمبير-متر16.31mV/A·m
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- الجهد الذي يُؤخذ منه حد الهبوط230V
AS/NZS 3000:2018 Cl 3.6.2
- حد هبوط الجهد11.5V
AS/NZS 3000:2018 Cl 3.6.2
- طول مسار هبوط الجهد35.26m
AS/NZS 3000:2018 Cl 3.6.2
- الطول الحاكمالنتيجة35.26m
AS/NZS 3000:2018 Cl 3.6.2
حول هذه الحاسبة
How this is calculated
The tool finds the longest final subcircuit route that two limits each allow. It reports which limit governs. It reads AS/NZS 3000:2018 and AS/NZS 3008.1.2:2017.
- Fault loop length. The tool reads the route length for your breaker, size and earth size from Table B1.
- Resistance and reactance. It reads these for the active conductor. The tables are Table 30 and Tables 34 and 35, for copper at operating temperature.
- Millivolts per ampere metre. It combines both values with your power factor.
- Voltage drop limit. Cl 3.6.2 sets the limit. You enter it as a percentage of the supply voltage.
- Voltage drop length. It finds the route length at which the drop equals the limit for your design current.
- Governing length. The shorter of the two lengths is the maximum route length.
| Step | Table or clause | What it decides |
|---|---|---|
| Fault loop length | AS/NZS 3000:2018 Table B1 | The longest route for the breaker to trip |
| Cable data | AS/NZS 3008.1.2:2017 Tables 30, 34 and 35 | Resistance and reactance |
| Voltage drop length | AS/NZS 3000:2018 Cl 3.6.2 | The longest route within the drop limit |
Worked example
- 2.5 mm² on a 20 A type B breaker. The earth is 2.5 mm², with PVC insulation, on a single‑phase 230 V supply. The design current is 20 A at a power factor of 0.9. The fault loop route length is 128 m. The voltage drop route length is 35.26 m. The voltage drop governs, so the maximum route length is 35.26 m.
Limits
The tool assumes copper conductors. The reactance is the Table 30 value for a multicore cable. A single‑core run reads a higher reactance for its formation.
The tool does not check the current rating of the cable. It does not add correction factors. Use the cable size calculator for the full check.
See also: Maximum length of a 20 A final subcircuit, The voltage drop limit in Cl 3.6.2 and the voltage drop calculator.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
ماذا تفعل أداة أقصى طول للدائرة؟
تعرض الأداة طولين. الأول هو طول المسار الذي لا يزال يسمح لجهاز الحماية بالفصل في الوقت المناسب. والثاني هو الطول الذي يبلغ عنده هبوط الجهد حدّك. الأقصر من الاثنين يحكم المسار.
من أين يأتي الطولان؟
يأتي طول حلقة العطل من AS/NZS 3000:2018 Table B1 لزمن فصل 0.4 s عند 230 V، مع تعديله حسب جهدك الاسمي. ويستخدم طول هبوط الجهد المقاومة والمفاعلة من AS/NZS 3008.1.2:2017 Tables 30 و34 و35، مقارنةً بـ Clause 3.6.2.
لماذا لا يظهر أي طول لحلقة العطل لتركيبة؟
يسرد Table B1 قائمة ثابتة من أزواج الموصلات وقيم الأجهزة الاسمية. الزوج غير المطبوع لا يملك طولًا في الجدول، لذلك تُبلغ الأداة عن طول هبوط الجهد فقط. استخدم أداة معاوقة الحلقة للتحقق من هذه التركيبة بدلًا من ذلك.
البنود والجداول التي تقرأها هذه الأداة
- B1Maximum route lengths for conductor sizes and protective devices
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 26 Sept 2026.
أدوات ذات صلة
- حاسبة مقاس الكابلFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة هبوط الجهدCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة معاوقة حلقة عطل التأريضCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000