Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 26 Sept 2026.
कोई प्रोजेक्ट आज़माएँ 6
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Find the longest run for a lighting circuitThe longest route a 1.5 mm² lighting circuit on a 10 A breaker can take.
- Find the longest socket circuitThe longest run for a 20 A circuit on 2.5 mm².
- Find the longest oven circuitThe longest run for a 32 A circuit on 6 mm², by voltage drop.
- Find the longest motor circuitThe longest three‑phase run on a 16 A D‑curve breaker.
- Find the longest run at 3 %The longest run when the drop limit is 3 %.
- Find the longest heat pump runThe longest run for a 16 A C‑curve circuit on 2.5 mm².
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- एक्टिव कंडक्टर
- 2.5 mm²
- अर्थ कंडक्टर
- 2.5 mm²
- इंसुलेशन
- PVC
- सुरक्षा उपकरण
- टाइप B सर्किट-ब्रेकर
- डिवाइस रेटिंग
- 20 A
- फ़ेज़
- सिंगल-फ़ेज़
- नॉमिनल फ़ेज़ वोल्टेज
- 230 V
- डिज़ाइन करंट
- 20 A
- पावर फ़ैक्टर
- 0.9
- वोल्टेज ड्रॉप सीमा
- 5 %
अधिकतम रूट लंबाई
35.26m
- फॉल्ट लूप मार्ग की लंबाई
- 128m
- वोल्टेज ड्रॉप मार्ग की लंबाई
- 35.26m
- गवर्निंग जाँच
- वोल्टेज ड्रॉप
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- फॉल्ट लूप मार्ग की लंबाई128m
AS/NZS 3000:2018 Table B1
- परिचालन तापमान पर तांबे के कंडक्टर का प्रतिरोध9.01Ω/km
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- रिएक्टेंस0.1Ω/km
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- प्रति एम्पियर मीटर वोल्टेज ड्रॉप16.31mV/A·m
AS/NZS 3008.1.2:2017 Table 30, Tables 34 to 35
- वह वोल्टेज जिससे ड्रॉप सीमा ली गई है230V
AS/NZS 3000:2018 Cl 3.6.2
- वोल्टेज ड्रॉप सीमा11.5V
AS/NZS 3000:2018 Cl 3.6.2
- वोल्टेज ड्रॉप मार्ग की लंबाई35.26m
AS/NZS 3000:2018 Cl 3.6.2
- गवर्निंग लंबाईपरिणाम35.26m
AS/NZS 3000:2018 Cl 3.6.2
इस कैलकुलेटर के बारे में
How this is calculated
The tool finds the longest final subcircuit route that two limits each allow. It reports which limit governs. It reads AS/NZS 3000:2018 and AS/NZS 3008.1.2:2017.
- Fault loop length. The tool reads the route length for your breaker, size and earth size from Table B1.
- Resistance and reactance. It reads these for the active conductor. The tables are Table 30 and Tables 34 and 35, for copper at operating temperature.
- Millivolts per ampere metre. It combines both values with your power factor.
- Voltage drop limit. Cl 3.6.2 sets the limit. You enter it as a percentage of the supply voltage.
- Voltage drop length. It finds the route length at which the drop equals the limit for your design current.
- Governing length. The shorter of the two lengths is the maximum route length.
| Step | Table or clause | What it decides |
|---|---|---|
| Fault loop length | AS/NZS 3000:2018 Table B1 | The longest route for the breaker to trip |
| Cable data | AS/NZS 3008.1.2:2017 Tables 30, 34 and 35 | Resistance and reactance |
| Voltage drop length | AS/NZS 3000:2018 Cl 3.6.2 | The longest route within the drop limit |
Worked example
- 2.5 mm² on a 20 A type B breaker. The earth is 2.5 mm², with PVC insulation, on a single‑phase 230 V supply. The design current is 20 A at a power factor of 0.9. The fault loop route length is 128 m. The voltage drop route length is 35.26 m. The voltage drop governs, so the maximum route length is 35.26 m.
Limits
The tool assumes copper conductors. The reactance is the Table 30 value for a multicore cable. A single‑core run reads a higher reactance for its formation.
The tool does not check the current rating of the cable. It does not add correction factors. Use the cable size calculator for the full check.
See also: Maximum length of a 20 A final subcircuit, The voltage drop limit in Cl 3.6.2 and the voltage drop calculator.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
अधिकतम सर्किट लंबाई टूल क्या करता है?
टूल दो लंबाइयाँ दिखाता है। पहली रूट की लंबाई है जो अभी भी प्रोटेक्टिव डिवाइस को समय पर डिस्कनेक्ट करने देती है। दूसरी वह लंबाई है जिस पर वोल्टेज ड्रॉप आपकी सीमा तक पहुँचता है। दोनों में से छोटी रन को तय करती है।
दो लंबाइयाँ कहाँ से आती हैं?
फ़ॉल्ट लूप लंबाई AS/NZS 3000:2018 Table B1 से 230 V पर 0.4 s डिस्कनेक्शन टाइम के लिए आती है, आपके नॉमिनल वोल्टेज के अनुपात में स्केल की गई। वोल्टेज ड्रॉप लंबाई AS/NZS 3008.1.2:2017 Tables 30, 34 और 35 का रेज़िस्टेंस और रिएक्टेंस उपयोग करती है, Clause 3.6.2 के विरुद्ध।
कॉम्बिनेशन फ़ॉल्ट लूप लंबाई क्यों नहीं दिखाता?
Table B1 में कंडक्टर जोड़ियों और डिवाइस रेटिंग की एक तय सूची सारणीबद्ध है। जो जोड़ी छपी नहीं है, उसकी सारणीबद्ध लंबाई नहीं होती, इसलिए टूल केवल वोल्टेज ड्रॉप की लंबाई दिखाता है। उस संयोजन की जाँच के लिए इसके बजाय लूप इम्पीडेंस टूल इस्तेमाल करें।
वे Clauses और Tables जो यह टूल पढ़ता है
- B1Maximum route lengths for conductor sizes and protective devices
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 26 Sept 2026 को जाँची गईं।
संबंधित टूल
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- वोल्टेज ड्रॉप कैलकुलेटरCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- अर्थ फ़ॉल्ट लूप इम्पीडेंस कैलकुलेटरCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।