In-service test limits for electrical equipment

The test and tag tool reads the pass limit for each in-service test from Tables 2.1, 2.2 and 2.3 and Clause 2.4.3.1: the earth circuit resistance, the leakage current and the insulation resistance for each equipment class, and the tripping time for each RCD type.

Verified: read against the printed standard, pages 15–17 (PDF 19–21). Checked 1 Oct 2026.

Units: Max ohm Ω, Max ma mA, Min mohm MΩ, Rated ma mA, Max trip ms ms

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3760:2022 page

12 rows

Table 2.1, 2.2, 2.3, In-service test limits for electrical equipment
CheckMax ohm (Ω)Max ma (mA)Min mohm (MΩ)Rated ma (mA)Max trip ms
earth-continuity1————
leakage-class-1—5———
leakage-class-2—1———
leakage-prcd-fe—5———
leakage-cord-set—1———
insulation-class-1——1——
insulation-class-2——1——
insulation-prcd-fe——0.05——
insulation-cord-set——1——
insulation-mi-heating——0.01——
rcd-type-1———1040
rcd-type-2———30300