Table 2.1, 2.2, 2.3

In-service test limits for electrical equipment

The test and tag tool reads the pass limit for each in-service test from Tables 2.1, 2.2 and 2.3 and Clause 2.4.3.1: the earth circuit resistance, the leakage current and the insulation resistance for each equipment class, and the tripping time for each RCD type.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 15–17 (PDF 19–21). I tirohia 1 Oct 2026.

Ngā unit: Max ohm Ω, Max ma mA, Min mohm MΩ, Rated ma mA, Max trip ms ms

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3760:2022

12 rārangi

Table 2.1, 2.2, 2.3, In-service test limits for electrical equipment
CheckMax ohm (Ω)Max ma (mA)Min mohm (MΩ)Rated ma (mA)Max trip ms
earth-continuity1————
leakage-class-1—5———
leakage-class-2—1———
leakage-prcd-fe—5———
leakage-cord-set—1———
insulation-class-1——1——
insulation-class-2——1——
insulation-prcd-fe——0.05——
insulation-cord-set——1——
insulation-mi-heating——0.01——
rcd-type-1———1040
rcd-type-2———30300