AS/NZS 3760:2022
Table 2.1, 2.2, 2.3
In-service test limits for electrical equipment
The test and tag tool reads the pass limit for each in-service test from Tables 2.1, 2.2 and 2.3 and Clause 2.4.3.1: the earth circuit resistance, the leakage current and the insulation resistance for each equipment class, and the tripping time for each RCD type.
Đã xác minh: đối chiếu với tiêu chuẩn in, trang 15–17 (PDF 19–21). Đã kiểm tra 1 Oct 2026.
Đơn vị: Max ohm Ω, Max ma mA, Min mohm MΩ, Rated ma mA, Max trip ms ms
Đây là các giá trị mà AmpSize mã hóa. Không sao chép nội dung tiêu chuẩn. Hãy đối chiếu với tiêu chuẩn hiện hành.
12 hàng
| Check | Max ohm (Ω) | Max ma (mA) | Min mohm (MΩ) | Rated ma (mA) | Max trip ms |
|---|---|---|---|---|---|
| earth-continuity | 1 | — | — | — | — |
| leakage-class-1 | — | 5 | — | — | — |
| leakage-class-2 | — | 1 | — | — | — |
| leakage-prcd-fe | — | 5 | — | — | — |
| leakage-cord-set | — | 1 | — | — | — |
| insulation-class-1 | — | — | 1 | — | — |
| insulation-class-2 | — | — | 1 | — | — |
| insulation-prcd-fe | — | — | 0.05 | — | — |
| insulation-cord-set | — | — | 1 | — | — |
| insulation-mi-heating | — | — | 0.01 | — | — |
| rcd-type-1 | — | — | — | 10 | 40 |
| rcd-type-2 | — | — | — | 30 | 300 |