AS/NZS 3760:2022
Table 2.4
Indicative testing and inspection intervals for electrical equipment
The test and tag tool reads the retest interval for each of the eight environments of Table 2.4, for the equipment itself and for the push-button and operating time tests of a portable or fixed RCD. A row says which of its cells the table prints as not applicable.
Verified: read against the printed standard, pages 21–23 (PDF 25–27). Checked 1 Oct 2026.
Units: Equipment months months, Rcd push portable months months, Rcd push fixed months months, Rcd time portable months months, Rcd time fixed months months
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
8 rows
| Env | Equipment months | Rcd push portable months | Rcd push fixed months | Rcd time portable months | Rcd time fixed months |
|---|---|---|---|---|---|
| 1 | 6 | — | 6 | 12 | 12 |
| 2 | 12 | 3 | 6 | 12 | 12 |
| 3 | 60 | 3 | 6 | 24 | 24 |
| 4 | 24 | 6 | 6 | 24 | 24 |
| 5 | 6 | — | — | 6 | — |
| 6 | 3 | — | — | 3 | 12 |
| 7 | — | — | — | — | — |
| 8 | — | — | — | — | — |