AS/NZS 3760:2022
Table 2.1, 2.2, 2.3
In-service test limits for electrical equipment
The test and tag tool reads the pass limit for each in-service test from Tables 2.1, 2.2 and 2.3 and Clause 2.4.3.1: the earth circuit resistance, the leakage current and the insulation resistance for each equipment class, and the tripping time for each RCD type.
已核验:对照印刷版标准阅读,页码 15–17 (PDF 19–21)。检查于 1 Oct 2026。
单位:Max ohm Ω, Max ma mA, Min mohm MΩ, Rated ma mA, Max trip ms ms
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
12 行
| Check | Max ohm (Ω) | Max ma (mA) | Min mohm (MΩ) | Rated ma (mA) | Max trip ms |
|---|---|---|---|---|---|
| earth-continuity | 1 | — | — | — | — |
| leakage-class-1 | — | 5 | — | — | — |
| leakage-class-2 | — | 1 | — | — | — |
| leakage-prcd-fe | — | 5 | — | — | — |
| leakage-cord-set | — | 1 | — | — | — |
| insulation-class-1 | — | — | 1 | — | — |
| insulation-class-2 | — | — | 1 | — | — |
| insulation-prcd-fe | — | — | 0.05 | — | — |
| insulation-cord-set | — | — | 1 | — | — |
| insulation-mi-heating | — | — | 0.01 | — | — |
| rcd-type-1 | — | — | — | 10 | 40 |
| rcd-type-2 | — | — | — | 30 | 300 |