AS/NZS 3760:2022
Table 2.1, 2.2, 2.3
In-service test limits for electrical equipment
The test and tag tool reads the pass limit for each in-service test from Tables 2.1, 2.2 and 2.3 and Clause 2.4.3.1: the earth circuit resistance, the leakage current and the insulation resistance for each equipment class, and the tripping time for each RCD type.
تم التحقق: مقروء مقابل المعيار المطبوع، الصفحات 15–17 (PDF 19–21). تم التحقق في 1 Oct 2026.
الوحدات: Max ohm Ω, Max ma mA, Min mohm MΩ, Rated ma mA, Max trip ms ms
هذه هي القيم التي ترمّزها AmpSize. لا يُعاد إنتاج أي نص من المعيار. تحقق من المعيار الحالي.
12 صفوف
| Check | Max ohm (Ω) | Max ma (mA) | Min mohm (MΩ) | Rated ma (mA) | Max trip ms |
|---|---|---|---|---|---|
| earth-continuity | 1 | — | — | — | — |
| leakage-class-1 | — | 5 | — | — | — |
| leakage-class-2 | — | 1 | — | — | — |
| leakage-prcd-fe | — | 5 | — | — | — |
| leakage-cord-set | — | 1 | — | — | — |
| insulation-class-1 | — | — | 1 | — | — |
| insulation-class-2 | — | — | 1 | — | — |
| insulation-prcd-fe | — | — | 0.05 | — | — |
| insulation-cord-set | — | — | 1 | — | — |
| insulation-mi-heating | — | — | 0.01 | — | — |
| rcd-type-1 | — | — | — | 10 | 40 |
| rcd-type-2 | — | — | — | 30 | 300 |