تخطَّ إلى المحتوى
AmpSize

This page is not in العربية yet, so you are reading the English.

· قراءة 1 دقيقة

How many amps can 2.5 mm² carry in Australia?

فحص الدائرة القائمة

+2 references

Worked to AS/NZS 3008.1.1:2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

التصنيف المصحح Iz

20A

أكبر جهاز بمنحنى C يسمح به الكابل
20A
هبوط الجهد
3.13%
أقصى Zs للجهاز
1.53Ω
فتح الحاسبة بهذه المدخلات

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

A drawn result card from the Circuit Check tool: circuit on 2.5 mm² passes.

2.5 mm² copper multicore PVC cable carries 20 A enclosed in air in Australia. The tool reads AS/NZS 3008.1.1:2025 Table 3.18 at its 40 °C air reference, with no derating. The largest curve C breaker it allows is 20 A, with no margin to spare.

The case

The circuit is single‑phase at 230 V and runs 20 m at the full 20 A of the breaker. The voltage drop is 3.13 % and the earth fault loop impedance is 0.71 Ω, inside the 1.53 Ω that Table 8.1 allows.

The circuit check reads Passes.

What changes the rating

Clipped direct to a surface, the cable carries 22 A.

The enclosed rating equals the breaker, so any derating fails a 20 A circuit on enclosed 2.5 mm². A grouped or insulated run needs the next size, or a smaller breaker.

See also: What size cable for power points in Australia? and AS/NZS 3008.1.1:2025 overview.

جرّبه بهذه المدخلات

درجة الحرارة المحيطة
40 °C
الأسلاك الداخلية
متعدد القلوب
منحنى الجهاز
المنحنى C
الإصدار
AS/NZS 3008.1.1:2025
الدوائر المجمّعة
1
العزل
PVC 75 °C
المعيار
AU · AS/NZS 3008.1.1
طول المسار
20 m
تيار التصميم
20 A
المادة
النحاس
طريقة التركيب
Enclosed in air
معامل القدرة
1
الأطوار
طور واحد
القيمة الاسمية للجهاز
20 A
حجم الكابل المركب
2.5 mm²
الجهد
230 V
المعاوقة الخارجية Ze
0.35 Ω
فتح الحاسبة بهذه المدخلات

الخطوة التالية

المفاهيم التي تقوم عليه

أمثلة محلولة إضافية

AmpSize أداة مساعدة للتصميم. تحقق من النتائج مقابل المعيار الحالي.

هل كان هذا مفيداً؟

سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.