How far can 4 mm² run on a 25 A circuit?

Maximum circuit length calculator

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 26 Sept 2026.

Pinakamahabang haba ng ruta

41m

Haba ng ruta ng fault loop
67m
Governing check
Voltage drop
Buksan ang calculator gamit ang mga input na ito

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

A drawn result card from the Maximum Circuit Length tool: maximum route length 41 m.

A 4 mm² copper circuit on a 25 A curve C breaker can run 41 m at its full load. Voltage drop sets that length: at 41 m the drop reaches the 5 % limit of AS/NZS 3000:2018 Cl 3.6.2.

The case

The circuit is single‑phase at 230 V with a 2.5 mm² earth and a design current of 25 A at a power factor of 1. AS/NZS 3000:2018 Table B1 gives a fault loop length of 67 m for this cable and device.

What changes the answer

The length scales with the load. With 20 A of design current on the same breaker, the run can reach 51.25 m. The fault loop length does not change with the load. It depends on the cable and the breaker.

See also: What size cable for a 25 A circuit? and Voltage drop basics.

Subukan gamit ang mga input na ito

Active conductor
4 mm²
Design current
25 A
Protective device
Type C circuit-breaker
Earth conductor
2.5 mm²
Insulation
PVC
Mga phase
Single phase
Power factor
1
Device rating
25 A
Limit ng voltage drop
5 %
Nominal phase voltage
230 V
Buksan ang calculator gamit ang mga input na ito