How far can 4 mm² run on a 25 A circuit?

最大回路长度计算器

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 26 Sept 2026.

最大路径长度

41m

故障回路路径长度
67m
控制性检查
电压降
使用这些输入打开计算器

此结果仅供设计参考。请对照现行标准进行核验。

A drawn result card from the Maximum Circuit Length tool: maximum route length 41 m.

A 4 mm² copper circuit on a 25 A curve C breaker can run 41 m at its full load. Voltage drop sets that length: at 41 m the drop reaches the 5 % limit of AS/NZS 3000:2018 Cl 3.6.2.

The case

The circuit is single‑phase at 230 V with a 2.5 mm² earth and a design current of 25 A at a power factor of 1. AS/NZS 3000:2018 Table B1 gives a fault loop length of 67 m for this cable and device.

What changes the answer

The length scales with the load. With 20 A of design current on the same breaker, the run can reach 51.25 m. The fault loop length does not change with the load. It depends on the cable and the breaker.

See also: What size cable for a 25 A circuit? and Voltage drop basics.