How far can 4 mm² run on a 25 A circuit?

Tātaitai Te Roa Nui Rawa o te Ara Iahiko

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 26 Sept 2026.

Roa teitei rawa o te huarahi

41m

Te roa o te ara o te loop hapa
67m
Tirotiro whakahaere
Heke voltage
Whakatuwhera te tātaitai me ēnei whakauru

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

A drawn result card from the Maximum Circuit Length tool: maximum route length 41 m.

A 4 mm² copper circuit on a 25 A curve C breaker can run 41 m at its full load. Voltage drop sets that length: at 41 m the drop reaches the 5 % limit of AS/NZS 3000:2018 Cl 3.6.2.

The case

The circuit is single‑phase at 230 V with a 2.5 mm² earth and a design current of 25 A at a power factor of 1. AS/NZS 3000:2018 Table B1 gives a fault loop length of 67 m for this cable and device.

What changes the answer

The length scales with the load. With 20 A of design current on the same breaker, the run can reach 51.25 m. The fault loop length does not change with the load. It depends on the cable and the breaker.

See also: What size cable for a 25 A circuit? and Voltage drop basics.

Whakamātau ki ēnei whakauru

Kaikawe active
4 mm²
Iahiko hoahoa
25 A
Taputapu whakamarutanga
Pōwhiri momo C
Kaikawe whenua
2.5 mm²
Insulation
PVC
Ngā wāhanga
Wāhanga kotahi
Power factor
1
Reiti taputapu
25 A
Rohe heke voltage
5 %
Voltage wāhanga ā-ingoa
230 V
Whakatuwhera te tātaitai me ēnei whakauru

Hei whai ake

Ngā whakaaro o muri i tēnei

Ētahi atu tauira mahi

He āwhina hoahoa a AmpSize. Arotakehia ngā otinga ki te paerewa o nāianei.

He whai hua tēnei?

He pātai, he uara rānei e kitea ana he hē? Whakapā mai.