حاسبة طريقة اللومن للإضاءة
عدد وحدات الإضاءة والشبكة لغرفة بطريقة اللومن.
Reads AS/NZS 1680.1:2006 and AS/NZS 1158.1.2:2010. Tables checked 1 Oct 2026.
جرّب مشروعاً 11
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Light a kitchen by the lumen methodHow many downlights a kitchen needs for its target lux, in a grid.
- Light a garage with battensHow many LED battens a garage needs, laid out in rows.
- Light an office to 320 lxHow many panels an office needs to AS/NZS 1680.1 Table 3.1, with the spacing check.
- Light a warehouse with high baysHow many 20 000 lm high bays a 30 by 20 m bay needs.
- Light a corridorHow many downlights a 12 by 1.5 m corridor needs.
- Light a bathroomHow many downlights a 3 by 2.4 m bathroom needs.
- Light a living roomHow many downlights a 6 by 4.5 m living room needs.
- Light a bedroomHow many downlights a 3.6 by 3.2 m bedroom needs.
- Light a switchroomHow many battens a 5 by 3 m switchroom needs.
- Light a classroom to 320 lxHow many panels a 9 by 7 m classroom needs at a target you set.
- Light a dusty workshopThe count with a maintenance factor from Table 14.4.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- استخدام الغرفة
- غرفة معيشة
- طول الغرفة
- 4 m
- عرض الغرفة
- 3.5 m
- ارتفاع السقف
- 2.4 m
- ارتفاع التجهيزة فوق الأرضية
- 0 m
- مستوى العمل
- 0 m
- الإضاءة المستهدفة
- 0 lx
- لومن لكل تركيبة إضاءة
- 800 lm
- واط لكل تركيبة إضاءة
- 9 W
- زاوية الشعاع
- 90 °
- معاملات الانعكاس: السقف / الجدران / الأرضية
- 70/50/20 %
- معامل صيانة التجهيزة من Table 14.4
- معامل خاص
- معامل الصيانة
- 0.8
تركيبات الإضاءة
6
- الشبكة
- 3 × 2
- التباعد طولًا
- 1.33m
- التباعد عرضًا
- 1.75m
- الإضاءة التي يحققها التخطيط
- 156lx
- كثافة القدرة للإضاءة
- 3.86W/m²
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- مساحة الأرضية14m²
- شدة الإضاءة المستهدفة150lx
Typical design value. Not a standard’s value.
- مستوى العمل0.7m
AS/NZS 1680.1:2006 Table 3.2
- ارتفاع المصباح2.4m
The ceiling
- الارتفاع فوق مستوى العمل1.7m
- مؤشر الغرفة
K = L × W / (Hm × (L + W))
1.1 - معامل الاستخدام0.57
Typical value for a direct luminaire. Use the maker’s table when you have it. Reflectances 70/50/20 %.
- معامل الصيانة0.8
- N = E × A / (Φ × UF × MF)5.76
- الشبكة3 by 2
- E' = N' × Φ × UF × MF / A156lx
- التباعد إلى الارتفاع، الأكبر1.03
Spacing to height ratio for even light. Typical.
- كثافة قدرة الإضاءة3.86W/m²
حول هذه الحاسبة
How this is calculated
The tool finds how many luminaires a room needs. It uses the lumen method. The target lux comes from AS/NZS 1680.1:2006 where that Standard lists the room use.
- Room and plane. The tool finds the floor area. It reads the target illuminance and the working plane height for the room use (Tables 3.1 and 3.2).
- Room index. It works out K = L × W / (Hm × (L + W)). Hm is the luminaire height above the working plane.
- Utilisation factor. It reads a typical factor for the room index and the reflectances you pick. You can type your own factor from the maker's table.
- Maintenance factor. It uses the value you give. The helper reads the luminaire factor from Table 14.4 of AS/NZS 1158.1.2:2010. You type the lamp lumen factor.
- Number of luminaires. N = E × A / (Φ × UF × MF). The tool rounds up to a grid that fits the room shape.
- Check. It works the lux the grid gives, the spacing to height ratio and the lighting power density.
| Step | Table or clause | What it decides |
|---|---|---|
| Target illuminance | AS/NZS 1680.1 Table 3.1 | The lux for the room use |
| Working plane | AS/NZS 1680.1 Table 3.2 | The height of the task plane |
| Maintenance factor | AS/NZS 1158.1.2 Table 14.4 | The luminaire factor for dirt |
Worked example
- Office, 6 m by 5 m, 3000 lm luminaires. The ceiling is 2.7 m. The target is 320 lx. The tool gives 9 luminaires in a 3 by 3 grid. That layout gives 449 lx.
Limits
- For a living room and some other uses, the target is a typical design value. It is not a Standard value. Check it against your brief.
- The utilisation factor is typical for a direct luminaire. Use the maker's table when you have it.
- The tool does not model glare, uniformity or a photometric file. It does not replace a lighting design programme.
- The grid is an even layout. A room with obstructions or a feature may need a different layout.
- The tool does not read AS/NZS 3008 and has no edition select.
See also: Worked examples by tool and trade, Obtrusive light and the 4282 zones and Obtrusive light.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
ماذا تفعل أداة طريقة اللومن للإضاءة؟
تحدد الأداة عدد وحدات الإضاءة التي تحتاجها الغرفة لشدة إضاءة مستهدفة. العدد هو الهدف مضروباً في مساحة الأرضية. ثم تقسم ذلك على لومن وحدة الإضاءة الواحدة والمعاملين الاثنين. ترتّب الأداة العدد في شبكة، وتتحقق من التباعد مقارنةً بارتفاع التركيب.
من أين تأتي شدة الإضاءة المستهدفة؟
تستند غرفة مكان العمل، مثل المكتب أو المستودع، إلى AS/NZS 1680.1:2006 Table 3.1، وتذكر الخطوة ذلك. غرف المنزل، ومطبخه وكراجه كذلك، تقع ضمن سلسلة AS/NZS 1680.2، وهي غير متضمنة في AmpSize. تستخدم هذه الغرف والمناطق الخارجية قيماً نموذجية، وتذكر الأداة ذلك. القيمة 240 lx في Table 3.1 مخصصة لتحضير الطعام في مكان العمل.
ما معامل الاستخدام؟
هو الجزء من ضوء المصباح الذي يصل إلى مستوى العمل. تقرأ الأداة قيمة نموذجية لوحدة إضاءة مباشرة. وتستخدم مؤشر الغرفة ومعاملات انعكاس السقف والجدار والأرضية. استخدم جدول الصانع عندما يتوفر لديك: اختر معامل الاستخدام الخاص بي وأدخل القيمة.
من أين يأتي عامل الصيانة؟
أدخل قيمتك الخاصة، أو خذ معامل صيانة وحدة الإضاءة من AS/NZS 1158.1.2:2010 Table 14.4. ذلك الجدول يستثني تدهور اللومن للمصباح. لذلك تطلب الأداة معامل صيانة لومن المصباح من ورقة البيانات: التصنيف L80 يعني 0.8. ومعامل الصيانة هو حاصل ضرب الاثنين.
أمثلة محلولة
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 1680.1:2006 Table 3.1Recommended maintained illuminances for various types of tasks, activities or interiors
- AS/NZS 1680.1:2006 Table 3.2Lighting parameters for general lighting: recommendations
- AS/NZS 1158.1.2:2010 Table 14.4Typical luminaire maintenance factors
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 1 Oct 2026.
أدوات ذات صلة
هل كان هذا مفيداً؟