跳至内容
AmpSize

照明光通量法计算器

按光通量法得出的房间灯具数量及布置网格。

Reads AS/NZS 1680.1:2006 and AS/NZS 1158.1.2:2010. Tables checked 1 Oct 2026.

输入

使用默认输入值的示例计算。

房间用途
客厅
房间长度
4 m
房间宽度
3.5 m
天花板高度
2.4 m
灯具距地面高度
0 m
工作面
0 m
目标照度
0 lx
每个灯具的流明数
800 lm
每个灯具的瓦数
9 W
光束角
90 °
反射率:天花板 / 墙面 / 地面
70/50/20 %
灯具维护系数取自 Table 14.4
自有系数
维护系数
0.8

灯具

6

网格
3 × 2
纵向间距
1.33m
横向间距
1.75m
布局所提供的照度
156lx
照明功率密度
3.86W/m²

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 楼面面积14m²
  2. 目标照度150lx

    Typical design value. Not a standard’s value.

  3. 工作面0.7m

    AS/NZS 1680.1:2006 Table 3.2

  4. 灯具高度2.4m

    The ceiling

  5. 高于工作面的高度1.7m
  6. 房间指数

    K = L × W / (Hm × (L + W))

    1.1
  7. 利用系数0.57

    Typical value for a direct luminaire. Use the maker’s table when you have it. Reflectances 70/50/20 %.

  8. 维护系数0.8
  9. N = E × A / (Φ × UF × MF)5.76
  10. 电网3 by 2
  11. E' = N' × Φ × UF × MF / A156lx
  12. 间距与高度之比,最大值1.03

    Spacing to height ratio for even light. Typical.

  13. 照明功率密度3.86W/m²

关于此计算器

How this is calculated

The tool finds how many luminaires a room needs. It uses the lumen method. The target lux comes from AS/NZS 1680.1:2006 where that Standard lists the room use.

  1. Room and plane. The tool finds the floor area. It reads the target illuminance and the working plane height for the room use (Tables 3.1 and 3.2).
  2. Room index. It works out K = L × W / (Hm × (L + W)). Hm is the luminaire height above the working plane.
  3. Utilisation factor. It reads a typical factor for the room index and the reflectances you pick. You can type your own factor from the maker's table.
  4. Maintenance factor. It uses the value you give. The helper reads the luminaire factor from Table 14.4 of AS/NZS 1158.1.2:2010. You type the lamp lumen factor.
  5. Number of luminaires. N = E × A / (Φ × UF × MF). The tool rounds up to a grid that fits the room shape.
  6. Check. It works the lux the grid gives, the spacing to height ratio and the lighting power density.
StepTable or clauseWhat it decides
Target illuminanceAS/NZS 1680.1 Table 3.1The lux for the room use
Working planeAS/NZS 1680.1 Table 3.2The height of the task plane
Maintenance factorAS/NZS 1158.1.2 Table 14.4The luminaire factor for dirt

Worked example

Limits

  • For a living room and some other uses, the target is a typical design value. It is not a Standard value. Check it against your brief.
  • The utilisation factor is typical for a direct luminaire. Use the maker's table when you have it.
  • The tool does not model glare, uniformity or a photometric file. It does not replace a lighting design programme.
  • The grid is an even layout. A room with obstructions or a feature may need a different layout.
  • The tool does not read AS/NZS 3008 and has no edition select.

See also: Worked examples by tool and trade, Obtrusive light and the 4282 zones and Obtrusive light.

问题

结果仅供设计参考。请依据现行标准核对。

照明光通量法工具有什么作用?

本工具求出房间达到目标照度所需的灯具数量。数量为目标照度乘以地板面积,再将其除以单个灯具的流明数及两个系数。本工具将数量排列成网格,并对照安装高度检查间距。

目标 lux 从哪里来?

办公室或仓库等工作场所房间依据 AS/NZS 1680.1:2006 Table 3.1,步骤中会注明。住宅房间、厨房和车库属于 AS/NZS 1680.2 系列,AmpSize 未收录该系列。这些房间及室外区域采用典型值,本工具会对此予以说明。Table 3.1 中的 240 lx 适用于工作场所食品准备。

利用系数是多少?

这是灯具光线到达工作面的部分。工具为直射式灯具读取典型值,并采用房间指数以及顶棚、墙面和地面的反射率。如有制造商表格,请选择“自定义利用系数”并输入数值。

维护系数从哪里来?

可自行输入,或从 AS/NZS 1158.1.2:2010 Table 14.4 取灯具维护系数。该表未计入光源光通量衰减。因此本工具要求从数据手册输入光源光通量维护系数:例如 L80 对应 0.8。维护系数为两者的乘积。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 1 Oct 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。