Công cụ tính chiếu sáng theo phương pháp quang thông
Số lượng đèn và lưới bố trí cho một phòng theo phương pháp quang thông.
Reads AS/NZS 1680.1:2006 and AS/NZS 1158.1.2:2010. Tables checked 1 Oct 2026.
Thử một công việc 11
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Light a kitchen by the lumen methodHow many downlights a kitchen needs for its target lux, in a grid.
- Light a garage with battensHow many LED battens a garage needs, laid out in rows.
- Light an office to 320 lxHow many panels an office needs to AS/NZS 1680.1 Table 3.1, with the spacing check.
- Light a warehouse with high baysHow many 20 000 lm high bays a 30 by 20 m bay needs.
- Light a corridorHow many downlights a 12 by 1.5 m corridor needs.
- Light a bathroomHow many downlights a 3 by 2.4 m bathroom needs.
- Light a living roomHow many downlights a 6 by 4.5 m living room needs.
- Light a bedroomHow many downlights a 3.6 by 3.2 m bedroom needs.
- Light a switchroomHow many battens a 5 by 3 m switchroom needs.
- Light a classroom to 320 lxHow many panels a 9 by 7 m classroom needs at a target you set.
- Light a dusty workshopThe count with a maintenance factor from Table 14.4.
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Công năng phòng
- Phòng khách
- Chiều dài phòng
- 4 m
- Chiều rộng phòng
- 3.5 m
- Chiều cao trần
- 2.4 m
- Chiều cao bộ đèn trên sàn
- 0 m
- Mặt phẳng làm việc
- 0 m
- Độ rọi mục tiêu
- 0 lx
- Lumen mỗi bộ đèn
- 800 lm
- Watt mỗi bộ đèn
- 9 W
- Góc chiếu
- 90 °
- Hệ số phản xạ, trần / tường / sàn
- 70/50/20 %
- Hệ số bảo trì bộ đèn lấy từ Bảng 14.4
- Hệ số riêng
- Hệ số bảo trì
- 0.8
Bộ đèn
6
- Lưới
- 3 × 2
- Khoảng cách dọc
- 1.33m
- Khoảng cách ngang
- 1.75m
- Độ rọi mà bố trí đạt được
- 156lx
- Mật độ công suất chiếu sáng
- 3.86W/m²
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Diện tích sàn14m²
- Độ rọi mục tiêu150lx
Typical design value. Not a standard’s value.
- Mặt phẳng làm việc0.7m
AS/NZS 1680.1:2006 Table 3.2
- Chiều cao đèn2.4m
The ceiling
- Chiều cao trên mặt phẳng làm việc1.7m
- Chỉ số phòng
K = L × W / (Hm × (L + W))
1.1 - Hệ số sử dụng0.57
Typical value for a direct luminaire. Use the maker’s table when you have it. Reflectances 70/50/20 %.
- Hệ số bảo trì0.8
- N = E × A / (Φ × UF × MF)5.76
- Lưới3 by 2
- E' = N' × Φ × UF × MF / A156lx
- Khoảng cách theo chiều cao, lớn nhất1.03
Spacing to height ratio for even light. Typical.
- Mật độ công suất chiếu sáng3.86W/m²
Giới thiệu công cụ tính này
How this is calculated
The tool finds how many luminaires a room needs. It uses the lumen method. The target lux comes from AS/NZS 1680.1:2006 where that Standard lists the room use.
- Room and plane. The tool finds the floor area. It reads the target illuminance and the working plane height for the room use (Tables 3.1 and 3.2).
- Room index. It works out K = L × W / (Hm × (L + W)). Hm is the luminaire height above the working plane.
- Utilisation factor. It reads a typical factor for the room index and the reflectances you pick. You can type your own factor from the maker's table.
- Maintenance factor. It uses the value you give. The helper reads the luminaire factor from Table 14.4 of AS/NZS 1158.1.2:2010. You type the lamp lumen factor.
- Number of luminaires. N = E × A / (Φ × UF × MF). The tool rounds up to a grid that fits the room shape.
- Check. It works the lux the grid gives, the spacing to height ratio and the lighting power density.
| Step | Table or clause | What it decides |
|---|---|---|
| Target illuminance | AS/NZS 1680.1 Table 3.1 | The lux for the room use |
| Working plane | AS/NZS 1680.1 Table 3.2 | The height of the task plane |
| Maintenance factor | AS/NZS 1158.1.2 Table 14.4 | The luminaire factor for dirt |
Worked example
- Office, 6 m by 5 m, 3000 lm luminaires. The ceiling is 2.7 m. The target is 320 lx. The tool gives 9 luminaires in a 3 by 3 grid. That layout gives 449 lx.
Limits
- For a living room and some other uses, the target is a typical design value. It is not a Standard value. Check it against your brief.
- The utilisation factor is typical for a direct luminaire. Use the maker's table when you have it.
- The tool does not model glare, uniformity or a photometric file. It does not replace a lighting design programme.
- The grid is an even layout. A room with obstructions or a feature may need a different layout.
- The tool does not read AS/NZS 3008 and has no edition select.
See also: Worked examples by tool and trade, Obtrusive light and the 4282 zones and Obtrusive light.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Công cụ Chiếu sáng theo phương pháp quang thông làm gì?
Công cụ tìm số đèn mà một phòng cần để đạt độ rọi mục tiêu. Số lượng bằng độ rọi mục tiêu nhân với diện tích sàn. Chia kết quả cho quang thông của một đèn và hai hệ số. Công cụ bố trí số lượng thành lưới và kiểm tra khoảng cách so với chiều cao lắp đặt.
Lux mục tiêu lấy từ đâu?
Phòng làm việc, như văn phòng hoặc kho, đọc AS/NZS 1680.1:2006 Table 3.1, và bước đó nêu tên nó. Các phòng trong nhà, cả bếp và gara, nằm trong bộ AS/NZS 1680.2, mà AmpSize không lưu. Các phòng này và khu vực ngoài trời dùng giá trị điển hình, và công cụ nêu rõ điều đó. 240 lx của Table 3.1 dành cho chế biến thực phẩm tại nơi làm việc.
Hệ số sử dụng là gì?
Đây là phần ánh sáng của đèn đến mặt phẳng làm việc. Công cụ đọc giá trị điển hình cho đèn chiếu trực tiếp. Công cụ dùng chỉ số phòng và hệ số phản xạ của trần, tường và sàn. Khi có bảng của nhà sản xuất, hãy dùng: chọn hệ số sử dụng riêng và nhập giá trị.
Hệ số bảo dưỡng lấy từ đâu?
Tự nhập, hoặc lấy hệ số bảo dưỡng bộ đèn từ AS/NZS 1158.1.2:2010 Table 14.4. Bảng đó không tính suy giảm quang thông của bóng đèn. Vì vậy công cụ yêu cầu hệ số bảo dưỡng quang thông của bóng từ bảng dữ liệu: định mức L80 cho giá trị 0.8. Hệ số bảo dưỡng là tích của hai hệ số này.
Các ví dụ tính sẵn
Nền
Các điều khoản và bảng mà công cụ này đọc
- AS/NZS 1680.1:2006 Table 3.1Recommended maintained illuminances for various types of tasks, activities or interiors
- AS/NZS 1680.1:2006 Table 3.2Lighting parameters for general lighting: recommendations
- AS/NZS 1158.1.2:2010 Table 14.4Typical luminaire maintenance factors
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 1 Oct 2026.