AmpSize

Cable fault rating calculator

Cable fault rating calculator for New Zealand and Australia. The k factor comes from AS/NZS 3008.1.2:2017, or AS/NZS 3008.1.1:2025 with 2017 selectable.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Prospective fault current
6 kA
Clearing time
0.1 s
Standard
NZ · AS/NZS 3008.1.2
Conductor size
25 mm²
Material
Copper
Insulation
PVC 75 °C
Insulation class
From the cable insulation
Joint in the run
No joint

Minimum conductor size

17.09mm²

Selected size
25mm²
Withstand fault current
8.78kA
k factor
111
Temperature limit
160°C

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Conductor start temperature75°CAS/NZS 3008.1.2:2017 Table 53
  2. Short-circuit temperature limit160°CAS/NZS 3008.1.2:2017 Table 53
  3. k factor111xAS/NZS 3008.1.2:2017 Table 52 p.121
  4. Minimum conductor size17.09mm²AS/NZS 3008.1.2:2017 Cl 5.3
  5. Withstand fault current8.78kAAS/NZS 3008.1.2:2017 Cl 5.3

About this calculator

How this is calculated

The tool checks that a conductor survives a fault current for the time the protective device takes to clear it. It uses the adiabatic equation, S = √(I²t) / k. It assumes that no heat leaves the conductor during the fault.

  1. Temperatures. It reads the start temperature and the short-circuit temperature limit for the insulation. The insulation class select can name a 110 °C cross-linked type. A joint in the run can set a lower limit than the insulation.
  2. k factor. It reads k from Table 52 for the conductor material and the two temperatures. A larger temperature rise gives a larger k.
  3. Minimum size. S = √(I²t) / k gives the smallest conductor, in mm², that stays within the limit. I is the fault current in amperes and t is the clearing time in seconds.
  4. Withstand. It turns the equation round for the size you pick: I = k × S / √t. That is the largest fault current the conductor survives for that time.
  5. Result. The size you pick passes when it is at or above the minimum.

The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Take the clearing time from the device curve at the fault current. A longer time needs a larger conductor.

StepTable or clauseWhat it decides
TemperaturesTable 53The start temperature and the limit for the insulation
JointTable 55A lower limit where the joint sets it
k factorTable 52The k for the material and the two temperatures
Minimum size and withstandCl 5.3The adiabatic check itself

Tables without a standard named are in the part of AS/NZS 3008.1 you pick.

Common faults, worked with the tool

Each line states its conductor. Every line uses copper and the New Zealand tables, with no joint unless the line names one.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What does the fault rating calculator do?

The tool applies the adiabatic check to a conductor. From the prospective fault current and the clearing time, it works out the minimum size. It also reports the fault current the entered size can withstand for that time. The check passes when the installed size is not below the minimum.

Where does the k factor come from?

The k factor comes from AS/NZS 3008.1.2:2017 Table 52. It depends on the conductor material and the insulation type. A failed check cites AS/NZS 3008.1.2:2017 Clause 5.3, which gives the adiabatic equation I²t = K²S². Change the material or the insulation and the k factor changes with it.

Which inputs matter most?

The prospective fault current and the clearing time drive the minimum size. The clearing time must match the device that clears the fault, not the downstream device. Material and insulation set the k factor. Cables in parallel are treated as one conductor of the combined cross section.

What does this check not cover?

The adiabatic method assumes that no heat leaves the conductor during the fault. It does not check the current rating, the voltage drop or the loop impedance. Use the cable size tool for those checks. The inputs sit in the page address, so a link reproduces the same check.

Does the conductor size or a joint change the k factor?

Yes. AS/NZS 3008.1.2:2017 Table 53 drops the thermoplastic limit from 160 to 140 degrees above 300 square millimetres. Table 55 limits a soldered joint to 160 degrees. The tool reads both, then takes the k factor for that start and limit pair from Table 52.

Worked examples

Background

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.