AS/NZS 5033:2021

Table 3.2

Nominal overcurrent rating of earth fault interrupter

The PV array tool reads the earth fault interrupter setting for the total array power, where the array has direct functional earthing.

Verified: read against the printed standard, pages 26 (PDF 34). Checked 1 Oct 2026.

Units: From kw kW, To kw kW, Setting A A

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 5033:2021 page

5 rows

Table 3.2, Nominal overcurrent rating of earth fault interrupter
From kw (kW)To kw (kW)Setting A
0251
25502
501003
1002504
250—5