AS/NZS 5033:2021
Table 3.2
Nominal overcurrent rating of earth fault interrupter
The PV array tool reads the earth fault interrupter setting for the total array power, where the array has direct functional earthing.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 26 (PDF 34). I tirohia 1 Oct 2026.
Ngā unit: From kw kW, To kw kW, Setting A A
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
5 rārangi
| From kw (kW) | To kw (kW) | Setting A |
|---|---|---|
| 0 | 25 | 1 |
| 25 | 50 | 2 |
| 50 | 100 | 3 |
| 100 | 250 | 4 |
| 250 | — | 5 |