AS/NZS 5033:2021
Table 4.1
Voltage correction factors for crystalline silicon PV modules
The PV string tool reads the voltage correction factor for the record low when you pick the table method. Verified on printed page 29.
Verified: read against the printed standard, pages 29 (PDF 37). Checked 1 Oct 2026.
Units: From C °C, To C °C, Factor x
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
13 rows
| From C (°C) | To C (°C) | Factor (x) |
|---|---|---|
| 24 | 20 | 1.02 |
| 19 | 15 | 1.04 |
| 14 | 10 | 1.06 |
| 9 | 5 | 1.08 |
| 4 | 0 | 1.1 |
| −1 | −5 | 1.12 |
| −6 | −10 | 1.14 |
| −11 | −15 | 1.16 |
| −16 | −20 | 1.18 |
| −21 | −25 | 1.2 |
| −26 | −30 | 1.21 |
| −31 | −35 | 1.23 |
| −36 | −40 | 1.25 |