AS/NZS 5033:2021
Table 3.2
Nominal overcurrent rating of earth fault interrupter
The PV array tool reads the earth fault interrupter setting for the total array power, where the array has direct functional earthing.
Na-verify: binasa laban sa naka-print na standard, mga pahina 26 (PDF 34). Na-check noong 1 Oct 2026.
Mga unit: From kw kW, To kw kW, Setting A A
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
5 na row
| From kw (kW) | To kw (kW) | Setting A |
|---|---|---|
| 0 | 25 | 1 |
| 25 | 50 | 2 |
| 50 | 100 | 3 |
| 100 | 250 | 4 |
| 250 | — | 5 |