AS/NZS 5033:2021 isolators, enclosures and earthing

PV array isolator, enclosure and earthing figures

The PV array tool reads the isolator ambient temperatures, the outdoor IP codes, the earthing sizes of Figure 4.13, the 0.5 ohm limit and the 120 V alarm threshold here.

Verified: read against the printed standard, pages 26, 37–39, 55, 65–67 (PDF 34, 45–47, 63, 73–75). Checked 1 Oct 2026.

Units: Value per row

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 5033:2021 page

15 rows

AS/NZS 5033:2021 isolators, enclosures and earthing, PV array isolator, enclosure and earthing figures
ClauseValue (per row)UnitPage
4.3.4.2.3(a)(i)40°C38
4.3.4.2.3(a)(ii)40°C38
4.3.4.2.3(a)(iii)60°C38
Table 4.556IP55
4.4.6.155IP55
4.4.6.2300mm55
Figure 4.1335V66
Figure 4.1316mm²66
Figure 4.134mm²66
Figure 4.134mm²66
Figure 4.134mm²66
4.6.50.5Ω65
Table 4.6120V67
Table 4.61.5m67
3.5.3120V26