AS/NZS 5033:2021
Table 3.2
Nominal overcurrent rating of earth fault interrupter
The PV array tool reads the earth fault interrupter setting for the total array power, where the array has direct functional earthing.
已核验:对照印刷版标准阅读,页码 26 (PDF 34)。检查于 1 Oct 2026。
单位:From kw kW, To kw kW, Setting A A
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
5 行
| From kw (kW) | To kw (kW) | Setting A |
|---|---|---|
| 0 | 25 | 1 |
| 25 | 50 | 2 |
| 50 | 100 | 3 |
| 100 | 250 | 4 |
| 250 | — | 5 |