Reduction factors for harmonic currents in 4- and 5‑core cables

The correction factors tool reads the reduction factor for third harmonic current in a four‑core or five-core cable. Above 33 %, it sizes on the neutral current. The harmonics tool reads the same band from a spectrum.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 27–28. I tirohia 24 Sept 2026.

Ngā unit: Third harmonic percent %, Factor x

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3008.1.2:2017

4 rārangi

Table 2, Reduction factors for harmonic currents in 4- and 5-core cables
BandMin percentMax percentFactor (x)Basis
0–15 %0151phase
15–33 %15330.86phase
33–45 %33450.86neutral
> 45 %451neutral