Lumaktaw sa nilalaman
AmpSize

AS/NZS 3008.1.2:2017

Table 2

Reduction factors for harmonic currents in 4- and 5‑core cables

The correction factors tool reads the reduction factor for third harmonic current in a four‑core or five-core cable. Above 33 %, it sizes on the neutral current. The harmonics tool reads the same band from a spectrum.

Na-verify: binasa laban sa naka-print na standard, mga pahina 27–28. Na-check noong 24 Sept 2026.

Mga unit: Third harmonic percent %, Factor x

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3008.1.2:2017

4 na row

Table 2, Reduction factors for harmonic currents in 4- and 5-core cables
BandMin percentMax percentFactor (x)Basis
0–15 %0151phase
15–33 %15330.86phase
33–45 %33450.86neutral
> 45 %451neutral

Mga tool na bumabasa nito (2)

Mga guide at learn page na nagbabanggit nito (2)