跳至内容
AmpSize

AS/NZS 3008.1.2:2017

Table 2

Reduction factors for harmonic currents in 4- and 5‑core cables

The correction factors tool reads the reduction factor for third harmonic current in a four‑core or five-core cable. Above 33 %, it sizes on the neutral current. The harmonics tool reads the same band from a spectrum.

已核验:对照印刷版标准阅读,页码 27–28。检查于 24 Sept 2026。

单位:Third harmonic percent %, Factor x

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3008.1.2:2017 页面上的对应卡片

4 行

Table 2, Reduction factors for harmonic currents in 4- and 5-core cables
BandMin percentMax percentFactor (x)Basis
0–15 %0151phase
15–33 %15330.86phase
33–45 %33450.86neutral
> 45 %451neutral

读取它的工具 (2)

引用本内容的指南和学习页面 (2)