What size cable for power points in NZ?

电缆截面计算器

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

导体规格

2.5mm²

降容后的容量
23A
电压降
3.92%
接地导体
2.5mm²
使用这些输入打开计算器

此结果仅供设计参考。请对照现行标准进行核验。

A drawn result card from the Cable Size tool: conductor size 2.5 mm².

A power point circuit on a 20 A breaker in New Zealand takes 2.5 mm² copper cable on a typical route. The route is 25 m of multicore PVC cable, enclosed in air at 30 °C, with no other circuit beside it. The tool gives 23 A of derated capacity and a voltage drop of 3.92 %.

The case

The circuit is single‑phase at 230 V. The design current is the full 20 A of the curve C breaker, at a power factor of 1. The voltage drop limit is 5 % and Ze is 0.35 Ω. Table 5.1 gives a 2.5 mm² earth, and the earth fault loop impedance is 0.8 Ω.

What changes the answer

Ceiling insulation changes it most. With the cable partly surrounded by insulation, the tool selects 4 mm² with 26 A of capacity.

Length is next. On a run of 40 m, voltage drop sets the size, and the tool selects 4 mm² with a drop of 3.9 %.

Before you install

Enter the real route: the installation method, the longest run and the circuits that share it. The tool prints each check with its clause or table.

See also: What size breaker for 4 mm² cable and Current-carrying capacity and derating.

使用这些输入试用

环境温度
30 °C
芯线
多芯
装置曲线
C 型曲线
检查保护装置
是
成组回路
1
绝缘
PVC 75 °C
敷设长度
25 m
设计电流
20 A
材料
铜
敷设方式
Enclosed in air
功率因数
1
相
单相
保护装置额定值
20 A
电压降限值
5 %
电压
230 V
外部阻抗 Ze
0.35 Ω
使用这些输入打开计算器

下一步

其背后的概念

更多示例