AS/NZS 3008.1.2:2017
Table 29
Rating factors for thermal resistivity of the soil
The cable size and correction factors tools read the factor for the thermal resistivity of the soil. It applies only to buried cables.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 90. I tirohia 24 Sept 2026.
Ngā unit: Resistivity K·m/W
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
8 rārangi
| Resistivity (K·m/W) | Multicore buried direct | Single core buried direct | Multicore in enclosure | Two single core in enclosure | Three single core in enclosure | Factor |
|---|---|---|---|---|---|---|
| 0.8 | 1.09 | 1.16 | 1.03 | 1.06 | 1.08 | 1.09 |
| 0.9 | 1.07 | 1.11 | 1.02 | 1.04 | 1.06 | 1.07 |
| 1 | 1.04 | 1.07 | 1.02 | 1.03 | 1.04 | 1.04 |
| 1.2 | 1 | 1 | 1 | 1 | 1 | 1 |
| 1.5 | 0.92 | 0.9 | 0.95 | 0.94 | 0.92 | 0.92 |
| 2 | 0.81 | 0.8 | 0.88 | 0.86 | 0.83 | 0.81 |
| 2.5 | 0.74 | 0.72 | 0.83 | 0.8 | 0.77 | 0.74 |
| 3 | 0.69 | 0.66 | 0.78 | 0.75 | 0.71 | 0.69 |