Whakawhiti ki te ihirangi
AmpSize

AS/NZS 3008.1.2:2017

Table 29

Rating factors for thermal resistivity of the soil

The cable size and correction factors tools read the factor for the thermal resistivity of the soil. It applies only to buried cables.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 90. I tirohia 24 Sept 2026.

Ngā unit: Resistivity K·m/W

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3008.1.2:2017

8 rārangi

Table 29, Rating factors for thermal resistivity of the soil
Resistivity (K·m/W)Multicore buried directSingle core buried directMulticore in enclosureTwo single core in enclosureThree single core in enclosureFactor
0.81.091.161.031.061.081.09
0.91.071.111.021.041.061.07
11.041.071.021.031.041.04
1.2111111
1.50.920.90.950.940.920.92
20.810.80.880.860.830.81
2.50.740.720.830.80.770.74
30.690.660.780.750.710.69

Ngā taputapu e pānui ana i tērā (3)

Ngā aratohu me ngā whārangi ako e whakahua ana i tēnei (4)