Table 3.48

Correction factors for soil thermal resistivity

The cable size, correction factors and DC cable size tools read the soil thermal resistivity factor here for a buried route.

Verified: read against the printed standard, pages 86. Checked 27 Sept 2026.

Units: Resistivity K·m/W

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.1:2025 page

8 rows

Table 3.48, Correction factors for soil thermal resistivity
Resistivity (K·m/W)Multicore buried directSingle core buried directMulticore in enclosureTwo single core in enclosureThree single core in enclosureFactor
0.81.091.161.031.061.081.09
0.91.071.111.021.041.061.07
11.041.071.021.031.041.04
1.2111111
1.50.920.90.950.940.920.92
20.810.80.880.860.830.81
2.50.740.720.830.80.770.74
30.690.660.780.750.710.69

Tools that read it (4)

Guides and learn pages that cite it (1)