AS/NZS 3008.1.1:2025

Table 3.34

Correction factors for single‑core circuits on trays, ladders, racks and cleats in air

On the 2025 edition, the cable size, correction factors and DC cable size tools read this table for single‑core circuits on a tray, a ladder, a rack or cleats. The values print the same as in 2017.

Verified: read against the printed standard, pages 74. Checked 27 Sept 2026.

Units: Tiers count, Count circuits per tier or row

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.1:2025 page

22 rows

Table 3.34, Correction factors for single-core circuits on trays, ladders, racks and cleats in air
ItemInstallationSpacingTiers (count)Factors
1unperforated-traystouching10.95, 0.85, 0.84
2unperforated-traystouching20.92, 0.83, 0.79
3unperforated-traystouching30.91, 0.82, 0.76
4perforated-traystouching10.97, 0.89, 0.87
5perforated-traystouching20.94, 0.85, 0.81
6perforated-traystouching30.93, 0.84, 0.79
7ladder-supports-racks-cleatstouching11, 0.95, 0.94
8ladder-supports-racks-cleatstouching20.95, 0.9, 0.88
9ladder-supports-racks-cleatstouching30.95, 0.89, 0.85
10vertical-perforated-traystouching10.94, 0.85, —
11vertical-perforated-traystouching20.92, 0.83, —
12unperforated-traysspaced10.95, 0.95, 0.94
13unperforated-traysspaced20.92, 0.91, 0.87
14unperforated-traysspaced30.91, 0.9, 0.85
15perforated-traysspaced10.97, 0.97, 0.96
16perforated-traysspaced20.94, 0.93, 0.89
17perforated-traysspaced30.93, 0.92, 0.86
18ladder-supportsspaced11, 1, 1
19ladder-supportsspaced20.95, 0.95, 0.93
20ladder-supportsspaced30.95, 0.94, 0.9
21vertical-perforated-traysspaced11, 0.91, 0.89
22vertical-perforated-traysspaced21, 0.9, 0.86