AS/NZS 3008.1.2:2017
Table 23
Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
The cable size and correction factors tools read the factor for single‑core circuits on a tray, a ladder, a rack or cleats. The factor depends on the support, the tiers, and whether the circuits touch.
تم التحقق: مقروء مقابل المعيار المطبوع، الصفحات 80. تم التحقق في 26 Sept 2026.
الوحدات: Tiers count, Count circuits per tier or row
هذه هي القيم التي ترمّزها AmpSize. لا يُعاد إنتاج أي نص من المعيار. تحقق من المعيار الحالي.
22 صفوف
| Item | Installation | Spacing | Tiers (count) | Factors |
|---|---|---|---|---|
| 1 | unperforated-trays | touching | 1 | 0.95, 0.85, 0.84 |
| 2 | unperforated-trays | touching | 2 | 0.92, 0.83, 0.79 |
| 3 | unperforated-trays | touching | 3 | 0.91, 0.82, 0.76 |
| 4 | perforated-trays | touching | 1 | 0.97, 0.89, 0.87 |
| 5 | perforated-trays | touching | 2 | 0.94, 0.85, 0.81 |
| 6 | perforated-trays | touching | 3 | 0.93, 0.84, 0.79 |
| 7 | ladder-supports-racks-cleats | touching | 1 | 1, 0.95, 0.94 |
| 8 | ladder-supports-racks-cleats | touching | 2 | 0.95, 0.9, 0.88 |
| 9 | ladder-supports-racks-cleats | touching | 3 | 0.95, 0.89, 0.85 |
| 10 | vertical-perforated-trays | touching | 1 | 0.94, 0.85, — |
| 11 | vertical-perforated-trays | touching | 2 | 0.92, 0.83, — |
| 12 | unperforated-trays | spaced | 1 | 0.95, 0.95, 0.94 |
| 13 | unperforated-trays | spaced | 2 | 0.92, 0.91, 0.87 |
| 14 | unperforated-trays | spaced | 3 | 0.91, 0.9, 0.85 |
| 15 | perforated-trays | spaced | 1 | 0.97, 0.97, 0.96 |
| 16 | perforated-trays | spaced | 2 | 0.94, 0.93, 0.89 |
| 17 | perforated-trays | spaced | 3 | 0.93, 0.92, 0.86 |
| 18 | ladder-supports | spaced | 1 | 1, 1, 1 |
| 19 | ladder-supports | spaced | 2 | 0.95, 0.95, 0.93 |
| 20 | ladder-supports | spaced | 3 | 0.95, 0.94, 0.9 |
| 21 | vertical-perforated-trays | spaced | 1 | 1, 0.91, 0.89 |
| 22 | vertical-perforated-trays | spaced | 2 | 1, 0.9, 0.86 |