AS/NZS 3008.1.2:2017
Table 23
Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
The cable size and correction factors tools read the factor for single‑core circuits on a tray, a ladder, a rack or cleats. The factor depends on the support, the tiers, and whether the circuits touch.
Đã xác minh: đối chiếu với tiêu chuẩn in, trang 80. Đã kiểm tra 26 Sept 2026.
Đơn vị: Tiers count, Count circuits per tier or row
Đây là các giá trị mà AmpSize mã hóa. Không sao chép nội dung tiêu chuẩn. Hãy đối chiếu với tiêu chuẩn hiện hành.
22 hàng
| Item | Installation | Spacing | Tiers (count) | Factors |
|---|---|---|---|---|
| 1 | unperforated-trays | touching | 1 | 0.95, 0.85, 0.84 |
| 2 | unperforated-trays | touching | 2 | 0.92, 0.83, 0.79 |
| 3 | unperforated-trays | touching | 3 | 0.91, 0.82, 0.76 |
| 4 | perforated-trays | touching | 1 | 0.97, 0.89, 0.87 |
| 5 | perforated-trays | touching | 2 | 0.94, 0.85, 0.81 |
| 6 | perforated-trays | touching | 3 | 0.93, 0.84, 0.79 |
| 7 | ladder-supports-racks-cleats | touching | 1 | 1, 0.95, 0.94 |
| 8 | ladder-supports-racks-cleats | touching | 2 | 0.95, 0.9, 0.88 |
| 9 | ladder-supports-racks-cleats | touching | 3 | 0.95, 0.89, 0.85 |
| 10 | vertical-perforated-trays | touching | 1 | 0.94, 0.85, — |
| 11 | vertical-perforated-trays | touching | 2 | 0.92, 0.83, — |
| 12 | unperforated-trays | spaced | 1 | 0.95, 0.95, 0.94 |
| 13 | unperforated-trays | spaced | 2 | 0.92, 0.91, 0.87 |
| 14 | unperforated-trays | spaced | 3 | 0.91, 0.9, 0.85 |
| 15 | perforated-trays | spaced | 1 | 0.97, 0.97, 0.96 |
| 16 | perforated-trays | spaced | 2 | 0.94, 0.93, 0.89 |
| 17 | perforated-trays | spaced | 3 | 0.93, 0.92, 0.86 |
| 18 | ladder-supports | spaced | 1 | 1, 1, 1 |
| 19 | ladder-supports | spaced | 2 | 0.95, 0.95, 0.93 |
| 20 | ladder-supports | spaced | 3 | 0.95, 0.94, 0.9 |
| 21 | vertical-perforated-trays | spaced | 1 | 1, 0.91, 0.89 |
| 22 | vertical-perforated-trays | spaced | 2 | 1, 0.9, 0.86 |