AS/NZS 3008.1.1:2025
Table 5.1
Values of constant K for determination of permissible short-circuit currents
This table gives one K per material and insulation. The cable size and fault rating tools read K from the short-circuit limits data instead.
Verified: read against the printed standard, pages 152. Checked 27 Sept 2026.
Units: K A·s^0.5/mm2
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
4 rows
| Material | Insulation | Initial temp C | Final temp C | K (A·s^0.5/mm2) |
|---|---|---|---|---|
| Cu | PVC | 75 | 160 | 111.2 |
| Cu | XLPE | 90 | 250 | 142.9 |
| Al | PVC | 75 | 160 | 73.7 |
| Al | XLPE | 90 | 250 | 94.6 |