AS/NZS 3008.1.1:2025
Table 5.1
Values of constant K for determination of permissible short-circuit currents
This table gives one K per material and insulation. The cable size and fault rating tools read K from the short-circuit limits data instead.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 152. I tirohia 27 Sept 2026.
Ngā unit: K A·s^0.5/mm2
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
4 rārangi
| Material | Insulation | Initial temp C | Final temp C | K (A·s^0.5/mm2) |
|---|---|---|---|---|
| Cu | PVC | 75 | 160 | 111.2 |
| Cu | XLPE | 90 | 250 | 142.9 |
| Al | PVC | 75 | 160 | 73.7 |
| Al | XLPE | 90 | 250 | 94.6 |