AS/NZS 3008.1.1:2017

Table 52

Values of constant K for determination of permissible short-circuit currents

This table gives one flat k factor per material and insulation. The cable size and fault rating tools read Table 52 from the short-circuit limits table instead. There, the k factor depends on the temperature limits Tables 53 and 55 set.

Verified: read against the printed standard, pages 121–122. Checked 19 Sept 2026.

Units: K A·s^0.5/mm2

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.1:2017 page

4 rows

Table 52, Values of constant K for determination of permissible short-circuit currents
MaterialInsulationInitial temp CFinal temp CK (A·s^0.5/mm2)
CuPVC75160111
CuXLPE90250143
AlPVC7516073.6
AlXLPE9025094.5