Skip to content
AmpSize

AS/NZS 3008.1.1:2025

Table 4.16, 4.18, 4.21, 4.23

d.c. voltage drop (mV/A.m) at the maximum conductor temperature

The DC cable size tool reads the d.c. mV/A.m of each size here. It multiplies that figure by the current and the route length.

Verified: read against the printed standard, pages 123, 126, 131, 134. Checked 27 Sept 2026.

Units: Mv per am mV/A.m

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.1:2025 page

20 rows

Table 4.16, 4.18, 4.21, 4.23, d.c. voltage drop (mV/A.m) at the maximum conductor temperature
SizeSingle core cu 75Single core cu 90Single core al 75Single core al 90Multicore cu 75Multicore cu 90Multicore al 75Multicore al 90
151.654.1——51.654.1——
1.533.134.7——33.134.7——
2.51818.9——1818.9——
411.211.8——11.211.8——
67.497.85——7.497.85——
104.454.67——4.454.67——
162.82.934.674.92.82.934.674.9
251.771.852.933.081.771.852.933.08
351.271.342.122.231.271.342.122.23
500.9410.9871.571.640.9410.9871.571.64
700.6520.6831.081.140.6520.6831.081.14
950.4690.4920.7820.8210.4690.4920.7820.821
1200.3720.390.6180.6490.3720.390.6180.649
1500.3020.3160.5030.5280.3020.3160.5030.528
1850.2410.2530.4010.4210.2410.2530.4010.421
2400.1830.1920.3050.3210.1830.1920.3050.321
3000.1460.1530.2440.2560.1460.1530.2440.256
4000.1140.120.190.1990.1140.120.190.199
5000.0890.09330.1480.1550.09070.09510.1510.158
6300.06880.07220.1150.12————

Tools that read it (1)