AS/NZS 3008.1.1:2025
Table 3.46, 3.47
Correction factors for depth of laying
The cable size, correction factors and DC cable size tools read the burial depth factor here for a buried route.
已核验:对照印刷版标准阅读,页码 85–86。检查于 27 Sept 2026。
单位:Depth m
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
10 行
| Depth (m) | Buried direct up to 50 | Buried direct 50 to 300 | Buried direct over 300 | Underground enclosure single core | Underground enclosure multicore | Factor |
|---|---|---|---|---|---|---|
| 0.5 | 1 | 1 | 1 | 1 | 1 | 1 |
| 0.6 | 0.99 | 0.98 | 0.97 | 0.98 | 0.99 | 0.99 |
| 0.8 | 0.97 | 0.96 | 0.94 | 0.95 | 0.98 | 0.97 |
| 1 | 0.95 | 0.93 | 0.92 | 0.93 | 0.96 | 0.95 |
| 1.25 | 0.94 | 0.92 | 0.89 | 0.91 | 0.95 | 0.94 |
| 1.5 | 0.93 | 0.9 | 0.87 | 0.89 | 0.94 | 0.93 |
| 1.75 | 0.92 | 0.89 | 0.86 | 0.88 | 0.94 | 0.92 |
| 2 | 0.91 | 0.88 | 0.85 | 0.87 | 0.93 | 0.91 |
| 2.5 | 0.9 | 0.87 | 0.84 | 0.86 | 0.92 | 0.9 |
| 3 | 0.89 | 0.85 | 0.82 | 0.85 | 0.91 | 0.89 |