AS/NZS 3000:2018

Cl 8.3.5.2 and 8.3.6.3

Insulation resistance and earth continuity verification limits

The test results and test schedule tools read the lowest insulation resistance and the highest earth continuity resistance a circuit may have.

Verified: read against the printed standard, pages 421–423. Checked 26 Sept 2026.

Units: Min mohm MΩ, Max ohm Ω, Test voltage V V

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

8 rows

Cl 8.3.5.2 and 8.3.6.3, Insulation resistance and earth continuity verification limits
CheckMin mohm (MΩ)Max ohm (Ω)Test voltage V
insulation-general1—500
insulation-sensitive1—250
sheathed-element0.01—500
rcd-functional-earth0.05—500
main-earth-bonding—0.5—
expected-pvc-50m-20c20—500
expected-pvc-50m-30c6—500
expected-xlpe-50m1500—500