Cl 5.3.3.1.3 Note 1

K values for the protective earthing conductor adiabatic equation

The earthing tool reads the k factor for the earthing conductor material and insulation. The factor sets the size the adiabatic equation returns for the fault current and time.

Verified: read against the printed standard, pages 277–278. Checked 26 Sept 2026.

Units: K A·s^0.5/mm2

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

2 rows

Cl 5.3.3.1.3 Note 1, K values for the protective earthing conductor adiabatic equation
KindK (A·s^0.5/mm2)
pvc-copper136
bare-copper170

Tools that read it (1)