AS/NZS 3000:2018

Cl 8.3.5.2 and 8.3.6.3

Insulation resistance and earth continuity verification limits

The test results and test schedule tools read the lowest insulation resistance and the highest earth continuity resistance a circuit may have.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 421–423. I tirohia 26 Sept 2026.

Ngā unit: Min mohm MΩ, Max ohm Ω, Test voltage V V

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

8 rārangi

Cl 8.3.5.2 and 8.3.6.3, Insulation resistance and earth continuity verification limits
CheckMin mohm (MΩ)Max ohm (Ω)Test voltage V
insulation-general1—500
insulation-sensitive1—250
sheathed-element0.01—500
rcd-functional-earth0.05—500
main-earth-bonding—0.5—
expected-pvc-50m-20c20—500
expected-pvc-50m-30c6—500
expected-xlpe-50m1500—500