AS/NZS 3000:2018
Cl 8.3.5.2 and 8.3.6.3
Insulation resistance and earth continuity verification limits
The test results and test schedule tools read the lowest insulation resistance and the highest earth continuity resistance a circuit may have.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 421–423. I tirohia 26 Sept 2026.
Ngā unit: Min mohm MΩ, Max ohm Ω, Test voltage V V
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
8 rārangi
| Check | Min mohm (MΩ) | Max ohm (Ω) | Test voltage V |
|---|---|---|---|
| insulation-general | 1 | — | 500 |
| insulation-sensitive | 1 | — | 250 |
| sheathed-element | 0.01 | — | 500 |
| rcd-functional-earth | 0.05 | — | 500 |
| main-earth-bonding | — | 0.5 | — |
| expected-pvc-50m-20c | 20 | — | 500 |
| expected-pvc-50m-30c | 6 | — | 500 |
| expected-xlpe-50m | 1500 | — | 500 |