AS/NZS 3000:2018
Cl 8.3.5.2 and 8.3.6.3
Insulation resistance and earth continuity verification limits
The test results and test schedule tools read the lowest insulation resistance and the highest earth continuity resistance a circuit may have.
已核验:对照印刷版标准阅读,页码 421–423。检查于 26 Sept 2026。
单位:Min mohm MΩ, Max ohm Ω, Test voltage V V
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
8 行
| Check | Min mohm (MΩ) | Max ohm (Ω) | Test voltage V |
|---|---|---|---|
| insulation-general | 1 | — | 500 |
| insulation-sensitive | 1 | — | 250 |
| sheathed-element | 0.01 | — | 500 |
| rcd-functional-earth | 0.05 | — | 500 |
| main-earth-bonding | — | 0.5 | — |
| expected-pvc-50m-20c | 20 | — | 500 |
| expected-pvc-50m-30c | 6 | — | 500 |
| expected-xlpe-50m | 1500 | — | 500 |