Skip to content
AmpSize

AS/NZS 3000:2018

I1

Protective device ratings for imperial cables in alterations and repairs

The imperial cable tool reads the protective device rating Table I1 allows for an old imperial conductor, by wire count and wire diameter, installation method, insulation temperature rating and device type. The table is for alteration and repair work.

Verified: read against the printed standard, pages 540–541. Checked 26 Sept 2026.

Units: Rating A, Diameter in in

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

14 rows

I1, Protective device ratings for imperial cables in alterations and repairs
SizeWiresDiameter inMethodV 75 cbV 75 fuseV 60 cbV 60 fuse
1/.04410.044unenclosed1310108
1/.04410.044partially-surrounded10886
3/.02930.029unenclosed16121310
3/.02930.029partially-surrounded138106
3/.03630.036unenclosed20161610
3/.03630.036partially-surrounded1610108
1/.06410.064unenclosed20161612
1/.06410.064partially-surrounded1610138
7/.02970.029unenclosed32202516
7/.02970.029partially-surrounded20161612
7/.03670.036unenclosed40253220
7/.03670.036partially-surrounded25202016
7/.04470.044unenclosed50324025
7/.04470.044partially-surrounded32252520

Tools that read it (1)

Guides and learn pages that cite it (1)