AS/NZS 3000:2018

Table C4

Upstream circuit loading after diversity

The circuit loading tool reads the diversity factor that Table C4 allows on the circuit upstream of a group of final subcircuits. The factor falls as the number of devices downstream rises. The load schedule tool reads it for each board of a site.

Verified: read against the printed standard, pages 475. Checked 26 Sept 2026.

Units: Factor x

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

4 rows

Table C4, Upstream circuit loading after diversity
MinMaxFactor (x)
230.9
450.8
690.7
10—0.6

Tools that read it (2)

Guides and learn pages that cite it (4)