AS/NZS 3000:2018
Table C4
Upstream circuit loading after diversity
The circuit loading tool reads the diversity factor that Table C4 allows on the circuit upstream of a group of final subcircuits. The factor falls as the number of devices downstream rises. The load schedule tool reads it for each board of a site.
Verified: read against the printed standard, pages 475. Checked 26 Sept 2026.
Units: Factor x
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
4 rows
| Min | Max | Factor (x) |
|---|---|---|
| 2 | 3 | 0.9 |
| 4 | 5 | 0.8 |
| 6 | 9 | 0.7 |
| 10 | — | 0.6 |